Decorah IA proposed data center ordinance (2026)
Decorah, IA — City Council Unanimously Passes First Reading of a Data Center Ordinance (M-3 Only, 500/750-ft Setbacks, 1,000-ft Water and Sinkhole Buffer, Closed-Loop Cooling, 55 dB Limit) (September 2026)
Decorah, IA · Decorah, IA — proposed data center / cryptocurrency mining zoning ordinance (first reading Sept. 2026)
- Status
- Proposed / pending
- Applies to
- Developers of data centers and cryptocurrency mining centers in Decorah
- Enforced by
- City of Decorah (City Council; Water and Public Works Departments)
Decorah's City Council unanimously advanced, on first reading, an ordinance that would allow data centers and cryptocurrency mining centers only in the M-3 General Industrial District under strict conditions. Buildings would need to be 500 feet from residential zones, and generators, substations and cooling equipment 750 feet. Facilities could not be within 1,000 feet of waterways, water sources, sinkholes or a 500-year floodplain, would have to use air-cooled or closed-loop cooling, and would face a 55-decibel noise limit at residential property lines. Additional readings are needed before it becomes law.
Who is protected: Decorah residents and water resources
Legal detail
First reading passed unanimously at the Monday council meeting reported Sept. 24, 2026 (Decorah News published Thu. Sept. 24, 2026 and says 'Monday' = Mon. Sept. 21, 2026). Scope: data centers and cryptocurrency mining centers; permitted in M-3 General Industrial. Setbacks: buildings 500 ft from residential zoning; backup generators, substations, cooling equipment 750 ft (greater when warranted). Prohibited within 1,000 ft of natural/public waterways, water sources, USGS-identified sinkholes or 500-year floodplain. Before a building permit: written utility verification of maximum electrical demand, available capacity, required infrastructure and effects on municipal utility operations. Water: air-cooled or closed-loop cooling; no groundwater/surface water for cooling unless Council approves after Water and Public Works review; projected demand and conservation plan; no on-site well (City Manager Travis Goedken). Noise: 55 dB (or 60 dBC) at property line adjacent to residential zoning; equipment specs; post-construction sound testing possible. Emergency/security: backup power, fire safety and emergency operations plans, controlled access, fencing, 24-hour monitoring, annual coordination with fire department. Decommissioning plan before construction; decommissioning may be required after 12 months of continuous non-operation. Council declined a moratorium (legal-defensibility concerns). NOT ESTABLISHED: ordinance number; dates of second/third readings.
Key facts
| Jurisdiction | Decorah, IA |
|---|---|
| Level | City / local |
| Citation | Decorah, IA — proposed data center / cryptocurrency mining zoning ordinance (first reading Sept. 2026) |
| Private right of action | No, agency enforcement only |
| Penalties | Not stated in the located sources |
| Topics | data-center siting and energy |
| News report | Decorah Council Moves to Regulate Data Centers with Strict Zoning, Utility and Environmental Standards — Decorah News |
Related data-center siting and energy rules elsewhere
- Superior WI Data Center Moratorium (1-year) · In effect
- Dane County WI Hyperscale Data Center Moratorium · In effect
- Madison WI Data Center Moratorium (1-year) · In effect
- Manitowoc County WI Data Center Moratorium · In effect
- WA SB 5982 (Data Center / Clean Energy) · In effect
- Dayton OH data center moratorium (180-day, Apr 2026) · In effect
See something wrong or out of date? Submit a correction. Every entry must carry a verifiable source.