Kokomo IN data center zoning standards (2026)

Kokomo, Indiana — Common Council Passes Data Center Zoning Standards 8-1: 350-Foot Residential Separation, 200-Foot Setbacks, No Night-Time Generator Testing, Decommissioning Plans (September 2026)
Kokomo, IN · Kokomo Common Council data center standards ordinance (passed Sept. 14, 2026)

Status
Enacted (not yet in effect)
Applies to
Data center developers and operators in Kokomo, apart from facilities under 1 MW critical IT load and 10,000 sq ft.
Enforced by
City of Kokomo (Plan Commission / zoning administration)

Kokomo's Common Council voted 8-1 on September 14, 2026 to adopt zoning standards for data centers. Before this, data centers were allowed by right and could be built 35 feet from a neighboring home. Under the new rules, data center buildings and substations must sit at least 350 feet from any existing home and 200 feet from property lines that border residential districts. Generator and equipment testing is banned between 5 p.m. and 7 a.m., mechanical equipment must be screened, a full build-out master site plan is required, and high-industrial developments must have decommissioning plans. Data centers remain allowed in all industrial zones and an office/institutional/agricultural overlay. Small facilities under 1 megawatt and 10,000 square feet are exempt. Residents who wanted an outright ban were not satisfied.

Who is protected: Kokomo residents living near industrial or overlay-zoned land where data centers may locate.

Legal detail

Kokomo, Indiana (Howard County) Common Council, data center standards ordinance (new zoning Section 6.75 drafted by HWC Engineering, per the Kokomo Tribune). First reading Monday, August 24, 2026 (Kokomo Tribune, August 25). Passed 8-1 at the September 14, 2026 meeting (Kokomo Lantern), with Councilman Bob Stephenson (D-2) dissenting, and then sent to Mayor Tyler Moore for signature. STANDARDS (Kokomo Lantern): data center structures, including electric substations, at least 350 ft from any existing residential structure; at least 200 ft setback from any property line abutting a residential district; transmission lines running parallel to a data center lot at least 100 ft from the lot boundary; no equipment or generator testing from 5 p.m. to 7 a.m.; roof- and ground-mounted mechanical equipment fully screened; a master site plan at initial application showing full build-out, phasing and added utility infrastructure; EXEMPTION for data centers with critical IT load under 1 MW and under 10,000 sq ft. ZONING: allowed in all industrial zones and in the OIA-OL (Office, Institutional, Agricultural Overlay) district. High-industrial developments are encouraged to use the most resource-efficient technology and must file a decommissioning plan, handled case by case. NOISE: no new data-center-specific noise rule; the existing ordinance caps sustained noise at 50 dB next to residential areas and 70 dB next to other zones, measured at the property line. PRIOR LAW: data centers were permitted by right with a 35-ft setback next to homes (HWC Engineering's Bryan Stumpf, Kokomo Tribune). NOT ESTABLISHED: ordinance number, the mayor's signature date, and the effective date.

Key facts

JurisdictionKokomo, IN
LevelCity / local
StrengthModerate
EnactedSeptember 14, 2026
CitationKokomo Common Council data center standards ordinance (passed Sept. 14, 2026)
Private right of actionNo, agency enforcement only
Topicsdata-center siting and energy